What size sauna heater do you need?
Put in the inside of the room. You’ll get the heater size, the circuit it needs and the running cost.
Updated · How we check our numbers
Heater for your sauna
6 kW heater
210 ft³ inside, counted as 265 ft³ for glass. It draws 25 A at 240 V.
- Room
- 265 ft³
- Circuit
- 30 A, 10 AWG
- At most
- $21/mo3×/wk, 1.5 h, full power
Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.
volume = 6 × 5 × 7 = 210 ft³
+ 14 ft² glass × 3.9 (Harvia)
Heaters by size
265 ft³- 4.5 kWAmerec 100–210, HUUM 106–247 ft³; 18.8 A at 240 V, 30 A breaker, 10 AWGToo small
- 6 kWAmerec 175–310, HUUM 177–353 ft³; 25 A at 240 V, 30 A breaker, 10 AWGPick
- 7.5 kWHUUM 247–424 ft³; 31.3 A at 240 V, 40 A breaker, 8 AWGAlso fits
- 8 kWAmerec 250–425 ft³; 33.3 A at 240 V, 8 AWGAlso fits
- 9 kWHUUM 282–530 ft³; 37.5 A at 240 V, 50 A breaker, 8 AWGToo big
Room ranges and wiring from Amerec and HUUM manuals. Running cost assumes full power the whole time; thermostats cut it.
HUUM and Amerec wire 6 kW on 10 AWG with a 30 A breaker. Saunacore sizes wire to 80% of its rating, which puts 6 kW on 8 AWG and 40 A. Your electrician and the heater’s own manual decide.
Measure the inside. Redwood Outdoors lists its 6-person barrel at 140 cu ft with a 6 kW heater; Amerec’s and HUUM’s 6 kW tables start at about 175 ft³.
How we work it out
room = length × width × height, + about 3.9 ft³ per ft² of glass, × 1.5 for log walls
Heater makers size by cubic feet. Harvia adds 1.2 m³ for every square meter of glass or uninsulated wall (about 3.9 ft³ per ft²), and multiplies a log sauna by 1.5; HUUM adds a bit more, 1.5 m³ per m². Then we match the room to Amerec's table (4.5 kW for 100 to 210 ft³, 6 kW for 175 to 310, 8 kW for 250 to 425) and HUUM's (4.5 kW for 106 to 247, 6 kW for 177 to 353, 7.5 kW for 247 to 424, 9 kW for 282 to 530).
Wiring is the maker's: HUUM puts 4.5 and 6 kW on a 30 A breaker with 10 AWG, 7.5 kW on 40 A with 8 AWG and 9 kW on 50 A with 8 AWG. Saunacore's manual sizes wire to 80% of its rating, which would put 6 kW on 8 AWG. Have an electrician follow your heater's manual.
Where the numbers come from
Guides
Sauna
More calculators
- Hot tubCan my deck hold it, and can my panel power it?
- Hot tub running costWhat does a hot tub cost to run?
- Hot tub costWhat does a hot tub cost installed?
- Cold plunge chillerWhat size chiller for my cold plunge?
- Sprinkler zonesHow many zones will my water pressure run?
- Water pressure and flow testWhat gpm and psi does my hose bib give me?
- Sprinkler layout plannerWhere do the heads go, and how many?
- Sprinkler run timeHow many minutes should each zone run?