Calculators / Hot tubs, saunas and plunges

What size sauna heater do you need?

Put in the inside of the room. You’ll get the heater size, the circuit it needs and the running cost.

Updated · How we check our numbers

These are example numbers. Put in yours.

The room

ft
ft
ft
sq ft

A glass door is about 14 sq ft.

Solid log walls?

Use and price

h

Including warm-up.

Heater for your sauna

6 kW heater

210 ft³ inside, counted as 265 ft³ for glass. It draws 25 A at 240 V.

Room
265 ft³
Circuit
30 A, 10 AWG
At most
$21/mo3×/wk, 1.5 h, full power

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

volume = 6 × 5 × 7 = 210 ft³

+ 14 ft² glass × 3.9 (Harvia)

Heaters by size

265 ft³
  • 4.5 kWAmerec 100–210, HUUM 106–247 ft³; 18.8 A at 240 V, 30 A breaker, 10 AWG
    Too small
  • 6 kWAmerec 175–310, HUUM 177–353 ft³; 25 A at 240 V, 30 A breaker, 10 AWG
    Pick
  • 7.5 kWHUUM 247–424 ft³; 31.3 A at 240 V, 40 A breaker, 8 AWG
    Also fits
  • 8 kWAmerec 250–425 ft³; 33.3 A at 240 V, 8 AWG
    Also fits
  • 9 kWHUUM 282–530 ft³; 37.5 A at 240 V, 50 A breaker, 8 AWG
    Too big

Room ranges and wiring from Amerec and HUUM manuals. Running cost assumes full power the whole time; thermostats cut it.

Wire for a 6 kW heater

HUUM and Amerec wire 6 kW on 10 AWG with a 30 A breaker. Saunacore sizes wire to 80% of its rating, which puts 6 kW on 8 AWG and 40 A. Your electrician and the heater’s own manual decide.

Barrel saunas

Measure the inside. Redwood Outdoors lists its 6-person barrel at 140 cu ft with a 6 kW heater; Amerec’s and HUUM’s 6 kW tables start at about 175 ft³.

How we work it out

room = length × width × height, + about 3.9 ft³ per ft² of glass, × 1.5 for log walls

Heater makers size by cubic feet. Harvia adds 1.2 m³ for every square meter of glass or uninsulated wall (about 3.9 ft³ per ft²), and multiplies a log sauna by 1.5; HUUM adds a bit more, 1.5 m³ per m². Then we match the room to Amerec's table (4.5 kW for 100 to 210 ft³, 6 kW for 175 to 310, 8 kW for 250 to 425) and HUUM's (4.5 kW for 106 to 247, 6 kW for 177 to 353, 7.5 kW for 247 to 424, 9 kW for 282 to 530).

Wiring is the maker's: HUUM puts 4.5 and 6 kW on a 30 A breaker with 10 AWG, 7.5 kW on 40 A with 8 AWG and 9 kW on 50 A with 8 AWG. Saunacore's manual sizes wire to 80% of its rating, which would put 6 kW on 8 AWG. Have an electrician follow your heater's manual.