Put in each run of lights: how long the cable is and how many lights are on it. You’ll get the transformer size and the cable gauge for every run, so the last light on each still gets enough voltage.

Updated · How we check our numbers

These are example numbers. Put in yours.

Path

ft

From the transformer to the last light, along the route the cable takes. Leave it blank to skip a run.

lights
W

Off the spec sheet. Blank uses Kichler 8" Dome LED's figure.

Garden and trees

ft

Transformer to the last light. Blank to skip.

lights
Light
W

Off the spec sheet. Blank uses Kichler MR16 lamp's or the light you picked figure.

Fence

ft

Transformer to the last light. Blank to skip.

lights
Light
W

Off the spec sheet. Blank uses Kichler Up & Down light, 2.3 W T5's or the light you picked figure.

Deck

ft

Transformer to the last light. Blank to skip.

lights
Light
W

Off the spec sheet. Blank uses Kichler Four Corners LED's or the light you picked figure.

Gazebo or pergola

ft

Transformer to the last light. Blank to skip.

lights
Light
W

Off the spec sheet. Blank uses Kichler Up & Down light, 2.3 W T5's or the light you picked figure.

String lights

ft

Transformer to the last light. Blank to skip.

lamps

A 12 V bistro string puts a lamp every 2 ft: 12 on a 24 ft strand.

W

Off the spec sheet. Blank uses Unique Lighting 12 V bistro's figure.

Transformer and wiring

How the lights sit on each run
Sizing rule

Your lighting plan

A 150 W transformer

36 fixtures, 87 W: VOLT says load it to 80% at most, so 108.7 W or more. 12 AWG cable does every run, and the 90 ft fence run drops 0.2 V.

Fixtures
36
Load
87 W129.4 VA
Transformer
150 WVOLT 80%: 108.7 W; Kichler: 155.3 W
See 150 W landscape lighting transformers on Amazon (opens Amazon in a new tab)

As an Amazon Associate we earn from qualifying purchases.

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

Measure each runTrace the path, fence and beds on the aerial photo to get the cable lengths.

load = 8 × 3 W + 4 × 5 W + 6 × 2.3 W + 6 × 0.9 W + 12 × 2 W = 87 W

VOLT: 87 W ÷ 0.8 = 108.7 W → 150 W

path: 36 VA × 60 ft × 1 ÷ 7500 (12 AWG) = 0.3 V

garden and trees: 26.4 VA × 50 ft × 1 ÷ 7500 (12 AWG) = 0.2 V

fence: 19.8 VA × 90 ft × 1 ÷ 7500 (12 AWG) = 0.2 V

deck: 11.2 VA × 30 ft × 1 ÷ 7500 (12 AWG) = 0.04 V

string lights: 36 VA × 40 ft × 1 ÷ 7500 (12 AWG) = 0.2 V

Each run

spread evenly (daisy chain), 12 V tap
  • Path, 60 ft8 × path light = 24 W (36 VA)
    12 AWG

    Drops 0.3 V: 11.7 V at the last light.

  • Garden and trees, 50 ft4 × spotlight, 5 W MR16 = 20 W (26.4 VA)
    12 AWG

    Drops 0.2 V: 11.8 V at the last light.

  • Fence, 90 ft6 × up and down light, 2.3 W lamp = 13.8 W (19.8 VA)
    12 AWG

    Drops 0.2 V: 11.8 V at the last light.

  • Deck, 30 ft6 × deck or step light = 5.2 W (11.2 VA)
    12 AWG

    Drops 0.04 V: 12 V at the last light.

  • String lights, 40 ft12 × string light lamp, 2 W S14 = 24 W (36 VA)
    12 AWG

    Drops 0.2 V: 11.8 V at the last light.

Drop = VA × feet × Kichler placement multiplier ÷ cable constant. 12 and 10 AWG constants from Kichler; 8 AWG from Vista.

Hub or daisy chain

A daisy chain is fine for these runs: every one stays inside the 1 V first-to-last spread Kichler calls best. VOLT says a daisy chain is OK for short chains, and a hub (one cable to a junction, equal leads to each light) evens out longer ones.

Multi-tap transformers

These cable sizes hold the last light at 10 V on the 12 V tap. A multi-tap transformer's 13, 14 or 15 V tap can make up more drop, but then the first lights on a run sit higher: Kichler wants LEDs between 10 and 14 V. Check with a meter at the last light.

Solar instead?

Solar path lights need no transformer, cable or trench, so they suit a spot you can't reach with wire. They are much dimmer: VOLT's own solar path light is rated 40 lumens, auto-dimming, against 250 for Kichler's 3 W wired path light, and they run only as long as the day's sun charged them. Low voltage is the one for lighting trees, a fence or a deck all evening.

Install

Plug the transformer into a GFCI outlet with an in-use cover, mount it at least 1 ft off the ground, and keep it 5 ft from a pool or spa and 10 ft from a fountain (VOLT). Kichler says to bury direct-burial cable at least 6 in, per the National Electrical Code.

Cable

Low-voltage landscape cable comes as 12/2, 10/2 and 8/2: two conductors of that gauge.

See 12/2 landscape cable on Amazon (opens Amazon in a new tab)

How we work it out

The transformer. We add up every light's watts. Default wattages come from Kichler's 2025 landscape catalog: 3 W for a path light, 0.86 W for a deck or step light, 4 to 7.2 W for an MR16 spotlight lamp. String lights use a 2 W S14 lamp from Unique Lighting's 12 V bistro string. VOLT says the fixtures should add up to no more than 80% of the transformer. Kichler's instructions size LED a little bigger, allowing for the drivers: LED watts ÷ 0.7 × 1.25. Pick either rule, and we round up to a size the makers sell.

VOLT: watts ÷ 0.8 · Kichler: watts ÷ 0.7 × 1.25

The cable. At 12 V a few volts lost in the cable is a big share, so every run is checked on its own. We use the makers' formula and cable constants, with the load in VA as Kichler does, because an LED's driver draws more than its watts. Kichler wants LEDs to see between 10 and 14 V, so on the 12 V tap a run can lose 2 V. We start at 12 AWG, the size Kichler says to start with, and go to 10 or 8 AWG when a run drops more.

drop = VA × cable feet × placement multiplier ÷ cable constant (12 AWG 7,500 · 10 AWG 11,920 · 8 AWG 18,960)

The placement multiplier is Kichler's: 1 when the lights are spread evenly along the cable, 0.75 when most are near the transformer, 1.25 when most are in the far half and 2 when they all sit at the end. A hub counts as the end: one cable runs out to a junction and each light gets its own lead.

Hub or daisy chain. On a daisy chain the first light gets more voltage than the last. Kichler calls a 1 V difference best and 2 V too much. VOLT says a daisy chain is fine for short chains, and that a hub with equal leads gives every light the same voltage. When a chained run goes past 1 V, we say so.

Not covered: halogen lamps, which need a narrower voltage than LEDs, and the higher taps on multi-tap transformers. Check the last light on each run with a meter once it's wired.